Compressor and condenser matching and selection
 Oct 31, 2019|View:110

According to the cooling area of the condenser, match the compressor model:

1. Calculation method of heat exchange area of air condenser

For example: (3ss1-1500 compressor)CT=40℃ : CE=-25℃ compressor refrigerating capacity =12527W+ compressor motor power 11250W=23777/230= air condenser heat exchange area 103m2


2. The ratio of heat exchange area of water condenser to air condenser = estimated ratio 1 to 18(103/18)=6m2

Evaporator area according to the compressor refrigerating capacity (evaporation temperature ℃ x Δ t relative humidity are coefficient of look-up table).


3. Calculation method of cooling capacity: = temperature difference × weight/time × specific heat × equipment maintenance mechanism

There is a freezer

1) library temperature 35 ℃

2) quick-freezing amount 1T/H

3) within time 2/H

4) quick-frozen substance (fresh fish)

5) ambient temperature 27℃

6) calculation of insulation board of equipment maintenance mechanism: 62℃×1000/2/H×0.82×1.23=31266 kcal/n


Contact Us
Tel: 0086-15961168909
Email: aaron@freezercold.com
Add: LuoYangtown, Changzhou, Jiangsu Province 
CHINA 213176
Get The Design Plan And Quotation
We provide professional customized services according to project requirements, please provide the information about your project, and we will provide you with a list immediately.
Company Name
*
This field is required
Email
*
This field is required
Email format error
Phone
This field is required
Telephone information is wrong!
Cold Room Size
Temperature
What will store in
Voltage/Frequency
Do you have the drawing
Message
*
This field is required
Send Message